Customized Solutions

ACS800-07 is built in a robust cabinet designed for heavy industrial applications.

The ACS800-07 offers a wide variety of standardized configurations to adapt to different application requirements, from line contactor to prevention of unexpected motor start.

If your application requires more, ABB's application engineering services can add special features to the standard product such as an additional cabinet for customer specific devices to ensure exact suitability for the application.

Smart Module Concept

The ACS800-07 drives consist of separate rectifier and inverter modules, which have plug-in power connectors providing easy maintenance and redundancy with parallel connected units. If one module becomes defective, the drive can continue running with reduced power after disconnecting the faulty module.

Extensive Range of Features

The ACS800-07 has an extensive range of built in features and options. Typical option choices include extended I/O and fieldbus options, line contactor, EMC filtering, common mode filtering and du/dt (voltage rise) output filtering, all mountable within the single cabinet.

Main Standard Features

  • Compact design
  • UL Type 1 protection class
  • Built in harmonic filtering choke
  • du/dt output filters
  • Common mode filters for motor protection
  • Line fuse disconnect switch
  • Extensive, programmable I/O
  • Inputs galvanically isolated
  • Long lifetime cooling fan and capacitors
  • 3 I/O and fieldbus extension slots inside
  • Alphanumeric multilingual control panel with start-up assistant feature
  • EMC filter for 2nd environment, unrestricted distribution according to EN 61800-3
  • Top entry and exit of cables

Back to Top


Ratings and Dimensions

  • Supply Voltages 380-500
  • Supply Voltages 525-690

3-phase supply voltage 380, 400, 415, 460, 480, 500.
The power ratings are valid at nominal voltage, 480Vac 60Hz

Type Designation Frame
Size
Input
A
Imax
A
I2N
A
PN
Hp
I2HD
A
PHD
Hp
Noise Level
dBA
Air Flow
ft3/min
Head Dissipation BTU/hr Click for Quote
ACS800-07-0760-5+C129+H3591D4+2R8i793132184870066055073183647800
ACS800-07-0910-5+C129+H3592D4+2R8i9441524100890078570074226058700
ACS800-07-1090-5+C129+H3592D4+2R8i113118821208100094180074226067900
ACS800-07-1210-5+C129+H3592D4+2R8i1233199113171150102690074226081200
ACS800-07-1540-5+A004+C129+H3592D4+3R8i159626551704150013281150752966100300
ACS800-07-1820-5+A004+C129+H3592D4+3R8i183129561956175015241250763390119400
ACS800-07-2310-5+A004+C129+H3593D4+4R8i240039012563225019971750764096154900

3-phase supply voltage 525, 575, 600, 690.
The power ratings are valid at nominal voltage, 575Vac 60Hz

Type Designation Frame
Size
Input
A
Imax
A
I2N
A
PN
Hp
I2HD
A
PHD
Hp
Noise Level
dBA
Air Flow
ft3/min
Head Dissipation BTU/hr Click for Quote
ACS800-07-0750-7+C129+H3591D4+2R8i56593960360047050073183647400
ACS800-07-0870-7+C129+H3591D4+2R8i655109170075054560073183658300
ACS800-07-1060-7+C129+H3591D4+2R8i795132485090066270073183662800
ACS800-07-1160-7+C129+H3592D4+2R8i8561426915100071380074226071000
ACS800-07-1500-7+C129+H3592D4+3R8i1131188212081250941100075296692100
ACS800-07-1740-7+C129+H3592D4+3R8i127121151357150010581150752966110900
ACS800-07-2120-7+C129+H3592D4+4R8i159526541703185013271400763672136800
ACS800-07-2320-7+A004+C129+H3593D4+4R8i167827921791200013961500764096147700
ACS800-07-2900-7+A004+C129+H3593D4+5R8i208634722228240017361900774803175700
ACS800-07-3190-7+A004+C129+H3593D4+6R8i239639872558280019932250785509197900
ACS800-07-3490-7+A004+C129+H3594D4+6R8i249041442659300020722300785933217000

Options for ASC800-07


Product Catalog

For a complete list of options and details, view the product catalog:
pdfACS800 Single Drives Catalog


  • Analog and digital I/O extension modules
  • Brake chopper and resistor
  • Cabinet heater
  • Customer terminal block
  • Ground fault monitoring for ungrounded network
  • EMC filter for 1st environment, restricted distribution according to EN 62800-3
  • EMC filter for 2nd environment, unrestricted distribution according to EN 61800-3
  • Fieldbus modules
  • UL Type 1 Filtered and UL Type 12 enclosure classes
  • Line contactor with emergency stop push button
  • Output for aux fan motor
  • Pulse encoder interface module
  • Prevention of unexpected start up of motor
  • 1 or 2 thermistor relays
  • 3, 5 or 8 PT100 relays
  • Resolver Interface (Limited SW Support)

Plus tailor made options through ABB's application engineering group.

Dimensions

Frame Size Width with line fuse switch & motor cabinet (in) UL Type 1 Height (in) UL Type 12 Height (in) Depth top entry/exit (in) Weight with line fuse switch (lbs)
1xD4+2xR8i83.983.991.125.42977
2xD4+2xR8i99.683.991.125.43485
2xD4+3xR8i111.483.991.125.43860
2xD4+4xR8i127.283.991.125.44390
3xD4+3xR8i13583.991.125.44590
3xD4+4xR8i150.883.991.125.45115
3xD4+5xR8i158.783.991.125.45465
3xD4+6xR8i190.283.991.125.45845
4xD4+6xR8i19883.991.125.46970

Notes

Imax current available for 10 seconds at start.
I2N continuous base current at 40º C (104º F).
Overload cycle 110% I2N for 1 minute / 5 minutes allowed.
I2HD continuous base current at 40º C (104º F).
Overload cycle 150% I2HD for 1 minute / 5 minutes allowed.


Current ratings do not change with different supply voltages.

The rated current of the ACS800 must be greater than or equal to the rated motor current to achieve the rated motor power given in the table.

Horsepower ratings are based on NEMA motor ratings for typical 4-pole motors (1800 rpm). Check motor nameplate current for compatibility.