ABB ACS800-X4, Single Drive Modules

ACS800-X4 units are complete single drive module products that are optimised for assembly in customers' own cabinets.

The single drive configuration contains a rectifier, DC link and an inverter in one single AC drive unit.

Single Drive Modules Diagram

The ACS800-X4 is designed to minimise the amount of cabinet space used and to make cabinet assembly as easy as possible. The power range is from 0.55 to 1900 kW.

ACS800-04 Single Drive Modules

ACS800-04 drives are single drive modules that are optimized for building into customers' own cabinets. They have been designed to minimise the cabinet space used, make cabinet assembly as easy as possible, and give maximum flexibility. The power range is from 0.55 to 1900 kW. All the drives, regardless of the power and voltage, have the same customer interface and I/O making system design and training easier.

The units have everything necessary built-in. That includes, for example, built-in chokes for harmonic filtering as standard, built-in braking chopper and built-in EMC filtering (both are optional in some frame sizes), making cabinet assembly easier. There is also a wide selection of different I/O and communications options.

In addition to these there is a selection of external accessories available.

To optimize the use of the cabinet space, most of the ACS800-04 modules can be mounted side by side. The modules themselves are not only designed for cabinet assembly, but covering documentation is also available. This documentation provides examples of different cabinet installations and circuit drawings, and hints on the selection of auxiliary equipment.

Optimized for Cabinet Assembly - Frame Sizes R2 to R6

The R2 to R6 frame size units are designed for cabinet wall mounting. The power range starts from 0.55 kW and extends up to 200 kW. The voltage range is from 230 to 690 V. The enclosure class of the modules is IP20 as standard.

Flange mounting is available as an option. It separates the airflow to the control section and the heatsink, and makes it possible to mount the heatsink of the drive outside the enclosure. With this option the heatsink side of the module has IP55 enclosure class. Safe torque-off (complies with the European Union machinery directive 2006/42/EC) is also available as option.

Compact Power - Frame Sizes R7 and R8

Frame size R7 and R8 modules have a very narrow bookshelf design. They are designed to be mounted either on the cabinet wall or floor. The power range is from 45 to 560 kW and the voltage range is from 230 to 690 V. The enclosure class is IP00.

The modules have top entry for the input power connections to optimise the use of space and cable routing in the cabinet. The output power connections are on the side to make access to the cables as easy as possible and to give sufficient space for cable bending. The outputs can be placed either on the left or right hand side of the module. I/O connections can be located in the most optimal place in the cabinet as they are in a separate unit.

ACS800-04M Variant - Frame Sizes R7 and R8

The ACS800-04M is similar in many respects to the frame size R7 and R8 ACS800-04, but it has even more variants available. For this reason the configuration rules are also different. In addition to the normal bookshelf mounting, the ACS800-04M also offers flat (sideways) mounting as an alternative for installations where the available depth inside the cabinet is limited. In frame size R7 the ACS800-04M also offers a version where the motor connections are from the bottom of the module. This makes it possible to use a narrower cabinet in some installations.

In addition to the normal IP00 enclosure, the ACS800-04M offers also IP20 as an option for some mounting variants. Safe torque-off (complies with the European Union Machinery Directive 2006/42/EC) is also available as option.

High Ratings - Frame Sizes D4 to n*D4 Supply Side and n*R8i Inverter Units

The construction includes separate IP00 enclosure supply and inverter modules. The modules are of the extremely compact bookshelf design, making the width of the drive very competitive. The wheels in every module make manoeuvring very easy. Modules are also connected to the separate cabling part by quick connectors, enabling each module to be pulled out quickly and easily by just disconnecting a couple of bolts without the need to disconnect any cables. The inverter modules and supply modules are parallel connected.

Supply units have load switch as standard; a contactor is also available as a built-in option. The supply module structure is designed to be either 6-pulse or 12-pulse.

The control unit and I/O connections can be located in the most optimal place in the cabinet as they are in a separate unit.

The power range for these higher rated ACS800-04 packages is from 400 to 1900 kW, and the voltage range is from 380 to 690 V.

ACS800-14 Single Drive Modules

The ACS800-14 drives are regenerative single drive modules equipped with active supply unit. They are full performance regenerative drives in a compact package. All important features and options including LCL line filter module(s), IGBT supply module(s), inverter module(s), common mode filters are in the package. The power range is from 75 to 1700 kW. All the drives, regardless of the power and voltage, have the same customer interface and I/O, making system design and training easier.

ACS800-X4 Drive Module

ACS800-04/-04M Features

Common

  • Optimised design for cabinet assembly
  • Easy access to power terminals
  • Compact design
  • Side by side mounting (excl. versions with side exit)
  • Harmonic filtering choke inside
  • Long lifetime cooling fan and capacitors
  • Extensive, programmable I/O with galvanically isolated inputs
  • Three I/O and fieldbus extension slots inside
  • Large power terminals allowing use of a wide range of cable sizes
  • Block programming possibility

Frame Sizes R2 to R6

  • Power range 0.55 to 200 kW
  • Voltage range 230 to 690 V
  • Mounting on the cabinet wall
  • IP20 enclosure class
  • Built-in brake chopper (R2 to R3; at 690 V also R4)
  • Easy access to I/O terminals (control board inside the module)

Frame Sizes R7 and R8

  • Power range 45 to 560 kW
  • Voltage range 230 to 690 V
  • Mounting on the cabinet wall or floor
  • IP00 enclosure class
  • Input power cable connection from the top for optimising cabinet size and cabling inside cabinet
  • Motor cable connection on the side of the module (side selectable) for maximized flexibility and optimised cabinet design (with ACS800-04M, frame size R7, bottom exit can also be selected)
  • Modular design allowing a wide variety of variants
  • Free location and easy access of I/O terminals (control board outside the module)
  • Instructions available for installing modules in Rittal TS8 cabinet

Frame Sizes nxD4 + nxR8i

  • Power range 400 to 1900 kW
  • Voltage range 380 to 690 V
  • Mounting on the cabinet floor
  • IP00 enclosure class
  • Wheels to make module manoeuvring easy
  • Load switch
  • du/dt filters inside of the module
  • Common mode filters for motor protection
  • Plug connector mechanical kits
  • Free location and easy access of I/O terminals (control board outside the module)

ACS800-14 Features

Standard Hardware Features

  • Frame sizes R7i to n*R8i control board outside of the module
  • Extensive, programmable I/O
  • Three I/O and fieldbus extension slots
  • Inputs galvanically isolated
  • Optimised design for cabinet assembly
  • Modular design allowing wide variety of variants
  • Compact design
  • Long lifetime cooling fan and capacitors
  • du/dt filters as standard in parallel connected R8i and in single or parallel connected 690 V inverter units
  • Mounting on the cabinet wall frame size R7i and on the cabinet floor for R8i
  • Wheels and plug connectors in the R8i inverter, and coated boards

Optional Hardware Features

Inverter Frame Size R7i

  • Prevention of unexpected start-up
  • DC fuses, fuse bases or DC-fuse switch
  • Assembly plates for R7i units
  • du/dt filters
  • Common mode filter for motor protection -on-off control for cooling fan with internal charging option

Inverter Frame Sizes
R8i to n*R8i

  • Prevention of unexpected start-up
  • DC fuses, fuse bases or DC-fuse switch + charging circuitry -du/dt filters as options in 400 / 500 V
  • Mechanical accessories in Rittal TS8 cabinets
  • IP21 to IP54 cabinet door / roof mechanical kits
  • Accessories kits
  • Common mode filters for motor protection

Back to Top


ACS800-04, 04M - Ratings and Dimensions

  • ACS800-04, UN = 230 V
  • ACS800-04, UN = 400 V
  • ACS800-04, UN = 500 V
  • ACS800-04, UN = 690 V

(Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.

Type Designation Icont. max
A
Imax
A
Pcont. max
kW
IN
A
PN
kW
Ihd
A
Phd
kW
Noise Level
dBA
Head Dissipation
W
Air Flow
m3/h
Frame Size Click for Quote
ACS800-04-0001-25.106.501.104.700.753.400.556210035R2
ACS800-04-0002-26.508.501.5061.104.300.756210035R2
ACS800-04-0003-28.5010.801.507.701.505.701.106210035R2
ACS800-04-0004-210.9013.802.2010.202.207.501.506212035R2
ACS800-04-0005-213.9017.60312.7039.302.206214035R2
ACS800-04-0006-2192441841436216069R3
ACS800-04-0009-225325.50245.501946220069R3
ACS800-04-0011-234467.50317.50235.506225069R3
ACS800-04-0016-24462114211327.5062340103R4
ACS800-04-0020-25572155011377.5062440103R4
ACS800-04-0025-2728618.506918.50491165530250R5
ACS800-04-0030-286112228022601565610250R5
ACS800-04-0040-21031383094226918.5065810250R5
ACS800-04-0050-214116437132379730651190405R6
ACS800-04-0060-2166202451554511530651190405R6
ACS800-04-0070-2202282551845514137651440405R6
ACS800-04(M)-0080-2214326552115517045712900540R7
ACS800-04(M)-0100-2253404752487520255713450540R7
ACS800-04(M)-0120-22954329029090240 4)55714050540R7
ACS800-04(M)-0140-2405588110396110316907253001220R8
ACS800-04(M)-0170-2447588132440132340907261001220R8
ACS800-04(M)-0210-25285881605161603701107267001220R8
ACS800-04(M)-0230-26138401605981604801327276001220R8
ACS800-04(M)-0260-26931017200679200590 2)1607278501220R8
ACS800-04(M)-0300-27201017200704200635 3)2007283001220R8

(Range 380 to 415 V). The power ratings are valid at nominal voltage 400 V.

Type Designation Icont. max
A
Imax
A
Pcont. max
kW
IN
A
PN
kW
Ihd
A
Phd
kW
Noise Level
dBA
Head Dissipation
W
Air Flow
m3/h
Frame Size Click for Quote
ACS800-04-0003-35.106.501.504.701.503.401.106210035R2
ACS800-04-0004-36.508.202.205.902.204.301.506212035R2
ACS800-04-0005-38.5010.8037.7035.702.206214035R2
ACS800-04-0006-310.9013.80410.2047.5036216035R2
ACS800-04-0009-313.9017.605.5012.705.509.3046220035R2
ACS800-04-0011-319247.50187.50145.506225069R3
ACS800-04-0016-32532112411197.506234069R3
ACS800-04-0020-3344615311523116244069R3
ACS800-04-0023-34046223918.5028156252069R3
ACS800-04-0025-34462224118.50321562530103R4
ACS800-04-0030-355723050223718.5062610103R4
ACS800-04-0035-35972305730412262660103R4
ACS800-04-0040-37286376930492265810250R5
ACS800-04-0050-386112458037603065990250R5
ACS800-04-0060-310313855100556937651190250R5
ACS800-04-75-3145170751417510045651440250R5
ACS800-04-0100-3166202901557511555651940405R6
ACS800-04-0120-32022821101849014175652310405R6
ACS800-04-135-322532611022011016390652810405R6
ACS800-04-0165-3260326132254132215110653260405R6
ACS800-04-0205-3290351160285160234132654200405R6
ACS800-04(M)-0140-320632611020211016390713000540R7
ACS800-04(M)-0170-3248404132243132202110713650540R7
ACS800-04(M)-0210-3289432160284160240 1)132714300540R7
ACS800-04(M)-0260-34455882004402003401607266001220R8
ACS800-04(M)-0320-35215882505162503702007271501220R8
ACS800-04(M)-0400-36028403155903154772507281001220R8
ACS800-04(M)-0440-36931017355679355590 2)3157286501220R8
ACS800-04(M)-0490-37201017400704400635 3)3557291001220R8
ACS800-04-0610-38791315500844500657400731300031201xD4+2xR8i
ACS800-04-0770-3111115216301067630831450741720038402xD4+2xR8i
ACS800-04-0870-3125518777101205710939500741850038402xD4+2xR8i
ACS800-04-1030-31452198880013948001086630742390038402xD4+2xR8i
ACS800-04-1230-3177026481000169910001324710752750050402xD4+3xR8i
ACS800-04-1540-3215629511200207012001613900763540057603xD4+3xR8i
ACS800-04-1850-32663398414502556145019921120764270069603xD4+4xR8i

(Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.

Type Designation Icont. max
A
Imax
A
Pcont. max
kW
IN
A
PN
kW
Ihd
A
Phd
kW
Noise Level
dBA
Head Dissipation
W
Air Flow
m3/h
Frame Size Click for Quote
ACS800-04-0004-54.906.502.204.502.203.401.506212035R2
ACS800-04-0005-56.208.2035.6034.202.206214035R2
ACS800-04-0006-58.1010.8047.7045.6036216035R2
ACS800-04-0009-510.5013.805.50105.507.5046220035R2
ACS800-04-0011-513.2017.607.50127.509.205.506225035R2
ACS800-04-0016-51924111811137.506234069R3
ACS800-04-0020-5253215231518116244069R3
ACS800-04-0025-5344618.503118.5023156253069R3
ACS800-04-0028-5384622372227196259069R3
ACS800-04-0030-542622239223218.5062610103R4
ACS800-04-0040-54872304430362262810103R4
ACS800-04-0045-55672375437392262950103R4
ACS800-04-0050-56586376137503065990250R5
ACS800-04-0060-5791124575456037651190250R5
ACS800-04-0070-5961385588556945651440250R5
ACS800-04-0105-5145170901419010055652150250R5
ACS800-04-0120-5157202901459011375652310405R6
ACS800-04-0140-518028211016311014190652810405R6
ACS800-04-0165-5225326132220132163110653260405R6
ACS800-04-0205-5260326160254160215132653800405R6
ACS800-04-0255-5290351200285200234160654500405R6
ACS800-04(M)-0170-5196326132192132162110713000540R7
ACS800-04(M)-0210-5245384160240160192132713800540R7
ACS800-04(M)-0260-5289432200284200224160714500540R7
ACS800-04(M)-0320-54405882504352503402007268501220R8
ACS800-04(M)-0400-55155883155103153702507278001220R8
ACS800-04(M)-0440-55508403555453554903157276001220R8
ACS800-04(M)-0490-5602840400590400515 2)3557281001220R8
ACS800-04(M)-0550-56841017450670450590 2)4007281001220R8
ACS800-04(M)-0610-57181017500704500632 3)4507297001220R8
ACS800-04-0760-58831321630848630660500731400031201xD4+2xR8i
ACS800-04-0910-5105015247101008710785560741720038402xD4+2xR8i
ACS800-04-1090-5125818829001208900941630741990038402xD4+2xR8i
ACS800-04-1210-5137219911000131710001026710742380038402xD4+2xR8i
ACS800-04-1540-5177526551250170412001328900752940050402xD4+3xR8i
ACS800-04-1820-52037595614501956140015241120763500057603xD4+3xR8i
ACS800-04-2310-52670390119002563185019971400764540069603xD4+4xR8i

(Range 525 to 690 V). The power ratings are valid at nominal voltage 690 V.

Type Designation Icont. max
A
Imax
A
Pcont. max
kW
IN
A
PN
kW
Ihd
A
Phd
kW
Noise Level
dBA
Head Dissipation
W
Air Flow
m3/h
Frame Size Click for Quote
ACS800-04-0011-713141111.507.508.505.5062300103R4
ACS800-04-0016-71719151511117.5062340103R4
ACS800-04-0020-7222818.502015151162440103R4
ACS800-04-0025-72538222318.50191562530103R4
ACS800-04-0030-733443030222218.5062610103R4
ACS800-04-0040-73654303430272262690103R4
ACS800-04-0050-75168454637343065840250R5
ACS800-04-0060-757845552454237651010250R5
ACS800-04-0070-7791047573555445651220405R6
ACS800-04-0100-7931249086756255651650405R6
ACS800-04-0120-7113172110108908675651960405R6
ACS800-04-0145-71341901321251109590652660405R6
ACS800-04-0175-7166245160155132131110653470405R6
ACS800-04-0205-7190245160180160147132654180405R6
ACS800-04(M)-0210-7166/2035)294160165/1955)160147132714250540R7
ACS800-04(M)-0260-7175/2305)326160/2005)175/2125)160/2005)163160714800540R7
ACS800-04(M)-0170-7166263160155132131110713550540R7
ACS800-04(M)-0140-71341901321251109590712800541R7
ACS800-04(M)-0320-73154333152902502162007261501220R8
ACS800-04(M)-0400-73535483553443152742507266501220R8
ACS800-04(M)-0440-73966564003873553283157274001220R8
ACS800-04(M)-0490-74457754504264003873557284501220R8
ACS800-04(M)-0550-74888535004824504264007283001220R8
ACS800-04(M)-0610-75609645605375004824507297501220R8
ACS800-04-0750-7628939630603630470500731390031201xD4+2xR8i
ACS800-04-0870-77291091710700710545560731710031201xD4+2xR8i
ACS800-04-1060-78851324800850800662630731840031201xD4+2xR8i
ACS800-04-1160-79531426900915900713710742080038402xD4+2xR8i
ACS800-04-1500-712581882120012081200941900752700050402xD4+3xR8i
ACS800-04-1740-71414211514001357140010581000753250050402xD4+3xR8i
ACS800-04-2120-71774265417001703170013271250764010062402xD4+4xR8i
ACS800-04-2320-71866279219001791180013961400764330069603xD4+4xR8i

Enclosure

Degree of protection:
IP00 standard for 04 and 04(M) frame sizes R7, R8 and nxR8i
IP20 standard for 04 frame sizes R2 to R6, option for some 04(M) variants
Paint color: RAL 9002/PMS 420C

Dimensions

Frame Size Height
mm
Width
mm
Depth
mm
Weight
kg
R2370165193 6)8
R3420173232 6)13
R4490240253 6)24
R560226527632
R670030039964
R71121/1152/1126 7)427/632/264 7)473/259/467 7)100
R81564/1596 8)562/779 8)568/403 8)205
D41480234400 10)180
2xD41480234 9)400 10)360
3xD41480234 9)400 10)540
2xR8i1397245 9)596300
3xR8i1397245 9)596450
4xR8i1397245 9)596600

Notes

1) 50% overload available if Tamb < 25 °C. If Tamb = 40 °C, max overload is 37%.
2) 50% overload available if Tamb < 30 °C. If Tamb = 40 °C, max overload is 40%.
3) 50% overload available if Tamb < 20 °C. If Tamb = 40 °C, max overload is 30%.
4) 50% overload available if Tamb < 35 °C. If Tamb = 40 °C, max overload is 45%.
5) Higher value available if output frequency is above 41 Hz.
6) Please note that use of control panel or I/O extension or communication options increases the depth.
7) Bookshelf (in ACS800-04M +H354) / flat (+H360) / bottom exit (+H352) version.
8) Bookshelf (in ACS800-04M +H354) / flat (+H360) mounting.
9) Single module only.
10) Cable connections need additional space (about 200 mm) behind the module.

Nominal Ratings

Icont. max: Rated current available continuously without overloadability at 40 °C.

Imax: Maximum output current. Available for 10s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd.

Typical Ratings: No-overload Use

Pcont. max: Typical motor power in no-overload use.

Light-overload Use

IN Continuous current allowing 110% IN for 1 min / 5 min at 40 °C.

PN Typical motor power in light-overload use.

Heavy-duty Use

Ihd: Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C.

Phd: Typical motor power in heavy-duty use.

The current ratings are the same regardless of the supply voltage within one voltage range.

The ratings apply at 40 °C ambient temperature. At higher temperatures (up to 50 °C) the derating is 1% / 1 °C.

Back to Top


ACS800-14 - Ratings and Dimensions

  • ACS800-14, UN = 400 V
  • ACS800-14, UN = 500 V
  • ACS800-14, UN = 690 V

(Range 380 to 415 V)

Type Designation Icont. max
A
Imax
A
Pcont. max
kW
IN
A
PN
kW
Ihd
A
Phd
kW
Noise Level
dBA
Head Dissipation
W
Air Flow
m3/h
Frame Size Click for Quote
ACS800-14-0140-32022931101949015175746.31300R7i+R7i+ALCL-04-5
ACS800-14-0170-325036313224013218790746.91300R7i+R7i+ALCL-05-5
ACS800-14-0210-32924001602801602181107573160R8i+R8i+ALCL-12-5
ACS800-14-0260-33705062002442002771327593160R8i+R8i+ALCL-13-5
ACS800-14-0320-346964225045025035120075113160R8i+R8i+ALCL-14-5
ACS800-14-0390-356577331554231542325075143160R8i+R8i+ALCL-15-5
ACS800-14-0490-370496340067535552625075193160R8i+R8i+ALCL-15-5
ACS800-14-0640-39191258500882500688355772264002xR8i+2xR8i+ALCL-24-5
ACS800-14-0770-3111115216301067630831450772864002xR8i+2xR8i+ALCL-25-5
ACS800-14-0960-31379188880013247101037560773664002xR8i+2xR8i+ALCL-25-5
ACS800-14-1070-315352102900147480011496307839102403xR8i+3xR8i+2xALCL-24-5
ACS800-14-1380-31978270712001899110014798007851102403xR8i+3xR8i+2xALCL-24-5
ACS800-14-1810-326103573160025061400195311007967128004xR8i+4xR8i+2xALCL-24-5

(Range 380 to 500 V)

Type Designation Icont. max
A
Imax
A
Pcont. max
kW
IN
A
PN
kW
Ihd
A
Phd
kW
Noise Level
dBA
Head Dissipation
W
Air Flow
m3/h
Frame Size Click for Quote
ACS800-14-0170-5200291132192132150907461300R7i+R7i+ALCL-04-5
ACS800-14-0210-52453561602351601831107481300R7i+R7i+ALCL-05-5
ACS800-14-0260-53023472002892002261327583160R8i+R8i+ALCL-12-5
ACS800-14-0320-536545725035025027316075103160R8i+R8i+ALCL-13-5
ACS800-14-0400-545553031543731534020075123160R8i+R8i+ALCL-14-5
ACS800-14-0460-552566035550435539325075143160R8i+R8i+ALCL-15-5
ACS800-14-0510-559564840057140044531575163160R8i+R8i+ALCL-15-5
ACS800-14-0580-567097250064345050431575193160R8i+R8i+ALCL-15-5
ACS800-14-0780-58921294630856630667450772464002xR8i+2xR8i+ALCL-24-5
ACS800-14-0870-510051458710956630752500772864002xR8i+2xR8i+ALCL-25-5
ACS800-14-1140-5131319069001261900982710773664002xR8i+2xR8i+ALCL-25-5
ACS800-14-1330-51528221711201467112011438007841102403xR8i+3xR8i+2xALCL-24-5
ACS800-14-1640-518842734140018091300140910007852102403xR8i+3xR8i+2xALCL-24-5
ACS800-14-2160-524863608180023871700186013007968128004xR8i+4xR8i+2xALCL-24-5

(Range 525 to 690 V)

Type Designation Icont. max
A
Imax
A
Pcont. max
kW
IN
A
PN
kW
Ihd
A
Phd
kW
Noise Level
dBA
Head Dissipation
W
Air Flow
m3/h
Frame Size Click for Quote
ACS800-14-0160-713219211012711099907471300R7i+R7i+ALCL-04-7
ACS800-14-0200-7150218132144132112907481300R7i+R7i+ALCL-05-7
ACS800-14-0260-720123820019316015013275113160R8i+R8i+ALCL-12-7
ACS800-14-0320-727931125026825020920075123160R8i+R8i+ALCL-13-7
ACS800-14-0400-733543131532225025120075163160R8i+R8i+ALCL-14-7
ACS800-14-0440-738250335536735528627075173160R8i+R8i+ALCL-15-7
ACS800-14-0540-744752545042940033431575183160R8i+R8i+ALCL-15-7
ACS800-14-0790-7659727630632630493450773264002xR8i+2xR8i+ALCL-24-7
ACS800-14-0870-7729985710700710545500773364002xR8i+2xR8i+ALCL-25-7
ACS800-14-1050-78961002900840800655350773664002xR8i+2xR8i+ALCL-25-7
ACS800-14-1330-7111214251120103711208318007848102403xR8i+3xR8i+2xALCL-24-7
ACS800-14-1510-7125614771250120612009409007851102403xR8i+3xR8i+2xALCL-24-7
ACS800-14-1980-716571879170015911600124012007967128004xR8i+4xR8i+2xALCL-25-7

Dimensions

Frame Size Height
mm
Width
mm
Depth 1)
mm
Weight
kg
R7i 1)96317040838
R8i1397245 2)596130
2xR8i1397245 2)596260
3xR8i1397245 2)596390
4xR8i1397245 2)596520
ALCL-0x-x81030429272
ALCL-1x-x1397240499180
ALCL-2x-x1397240573305

Notes

1) Dimensions do not include the cooling fan
2) Single module only

Options

View the ACS800 Drive Modules Catalog for options.

Nominal Ratings

Icont. max: Rated current available continuously without overloadability at 40 °C.

Imax: Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd.

Typical Ratings: No-overload Use.

Pcont. max: Typical motor power in no-overload use.

Light-overload Use

IN: Continuous current allowing 110% of IN for 1 min / 5 min at 40 °C.

PN: Typical motor power in light-overload use.

Heavy-duty Use

Ihd: Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C.

Phd: Typical motor power in heavy-duty use.

The current ratings are the same regardless of the supply voltage within one voltage range.

The ratings apply at 40 °C ambient temperature. At higher temperatures (up to 50 °C) the derating is 1% / 1 °C.